The following Uninterruptible Power Supply (UPS) systems are at End-OF-Service-Life (EOSL) or approaching that date, and parts may not be available: R3000XR R/T3000 R/T3000 G2 R/T3000 G4 UPS Note: All units may be out of warranty, except units that are under extended service contracts; this applies to extended service agreements only. Verify warranty status before requesting a replacement.
The following Uninterruptible Power Supply (UPS) systems are affected: R3000XR R/T3000 R/T3000 G2 R/T3000 G4 UPS Note: The differences between each of the systems are summarized on this document.
When the parts are totally depleted from stock as they became End-OF-Service-Life (EOSL), replace the HPE R3000XR, R/T3000, R/T3000 G2 and R/T3000 G4 model with the R/T3000 G5 model. UPS Models Comparison Table UPS Name R3000XR R/T3000 R/T3000 G2 R/T3000 G4 R/T 3000 G5 Part numbers 407390-001, 407391-001, 407392-291, 407395-002, 407397-291 517699-001 517700-001 517701-001 638840-001 638841-001 638842-001 796758-001 796759-001 796760-001 881408-001*,881409-001*,881410-001* *These PNs do not include the batteries. They must be ordered separately. (The Batt Mod. PN is 796777-001) Refer to Advisory with Doc. ID: a00045716en_us Power output (Watts) NA LV (Japan), NA HV, Intl 2700 (2250W), 2700W, 2700W 2700W (2250W), 2700W, 2700W 2700W (2250W), 2700W, 2700W 2700W, (2250W) 2700W, 2700W 2700W, (2250W)2700W,2700W Dimensions(WidthxDepthxHeight, inches) 17.5"x25.0"x3.5" 17.5"x25.0"x3.5" 17.5"x25.0"x3.5" 17.5"x 25.5"x 3.5" 17.5"x 25.5"x 3.5" Weight(lbs.) 82 82 82 87 87 Battery runtime 100% load 5 min 5 min (LV) and 4min (HV) 5 min (LV) and 4min (HV) 3 min 3 min Communication card AF401A AF401A AF465A AF465A Q1C17A User interface s/w HPPM HPPM HPPP HPPP HPEPP Extended Runtime Module 407398-001 517702-001 517702-001 796762-001 796762-001 Internal Battery module 407407-001 517703-001 517703-001 796777-001 796777-001 Important Notes: The RT3000 G5 UPS is essentially the same UPS as the RT3000 G4 UPS, except for the following changes: New front bezel with new HPE green rectangle logo element. Updated internal circuit boards to accommodate new communication card (Quark2). Replacing the R3000XR with R/T3000 G5 models When the R3000XR UPS is replaced with the R/T3000 G5 UPS, there are eight differences between both UPSs: Front panel cosmetic differences. The R/T3000 G5 UPS is cosmetically different from the R3000XR. See illustrations below for reference only. R3000XR vs R/T3000 G5 Rear panel receptacles and cable differences. See the following illustrations for reference only. R3000XR vs R/T3000 The R/T3000 G5 UPS has a different quantity of rear panel outlets. Refer to the Table below: R3000 XR Legacy to R/T3000 G5 Compatibility Matrix R3000 XR Legacy Option Kit R3000 XR Legacy Option Kit Description R3000 XR Legacy Spare Unit R3000 XR Legacy Spare Unit Description Replacement Alternative R/T3000 G5 Unit Spare R3000 XR Legacy Output Receptacles Alternative R/T3000 G5 Output Receptacles AF422A KIT,OPT,R3KVA UPS L530,NA 407390-001 SPS-UPS,R3KVA,2U,L530-NA 881408-001 + Batt. 796777-001 (6) 5-15R & (1) L5-30R (6) 5-20R & (1) L5-30P AF425A KIT,OPT,R3KVA UPS L530,JPN 407392-291 SPS-UPS,R3KVA,2U,L530-JP 881408-001 + Batt. 796777-001 (6) 5-15R & (1) L5-30P (6) 5-20R & (1) L5-30P AF414A KIT,OPT,R3KVA UPS DTC,INTL 407395-002 SPS-UPS,R3KVA,2U,DTC-INTL 881410-001+ Batt. 796777-001 (9) C13 & (1) C20 (8) C13 & (1) C19 AF423A KIT,OPT,R3KVA UPS L620H,NA 407391-001 SPS-UPS,R3KVA,2U,L620H-NA 881409-001+ Batt. 796777-001 (9) C13 & (1) L6-20R (8) C13 & (1) C19 AF424A KIT,OPT,R3KVA UPS L620H,JPN 407393-391 SPS-UPS,R3KVA,2U,L620H-JPN 881409-001+ Batt. 796777-001 (9) C13 & (1) L6-20R (8) C13 & (1) C19 The R/T3000 G5 UPS uses different internal batteries than the R3000XR. R/T3000 G5 battery: 796777-001 R3000XR battery: 407407-001 The R/T3000 G5 Extended Runtime Module (ERM) is different from the R3000XR. A customer's existing R3000XR ERM (407398-001) will NOT function with the R/T3000 G5. The R/T3000 G5 requires a 796762-001 ERM. Runtime (under full load): R3000XR runtime: 5 min R/T3000 G5 runtime: 3 min Communication card: R3000XR uses the HP Management Card AF401A R/T3000 G5 uses a Q1C17A Software User Interface: R3000XR uses HPPM (HP Power Management) R/T3000 G5 uses HPEPP (HPE Power Protector) Replacing the R/T3000 with R/T3000 G5 models When the R/T3000 UPS units are replaced with the R/T3000 G5 UPS, there are eight differences between both UPS units: Front panel cosmetic differences. The R/T3000 G5 UPS is cosmetically different from the R/T3000. See the illustrations below for reference only. R/T3000 vs R/T3000 G5 Rear panel receptacles and cable differences. See the following illustrations for reference only. R/T3000 vs R/T3000 G5 The R/T3000 G5 UPS has a different quantity of rear panel outlets. Refer to the Table below: R/T3000 to R/T3000 G5 Compatibility Matrix R/T3000 Option Kit R/T3000 Option Kit Description R/T3000 Spare Unit R/T3000 Spare Unit Description Replacement Alternative R/T3000 G5 Unit Spare R/T3000 G1 Output Receptacles Alternative R/T3000 G5 Output Receptacles AF452A R/T 3KVA UPS, 2U, L530, LV, NA/JPN KIT 517699-001 SPS-UPS, R3KVA, L5-30P, 2U, NA/JPN 881408-001+ Batt. 796777-001 (4) 5-20T & (1) L5-30R (6) 5-20R & (1) L5-30R AF453A R/T 3KVA UPS, 2U, L620, HV, NA/JPN KIT 517700-001 SPS-UPS, R3KVA, L6-20P, 2U, NA/JPN 881409-001+ Batt. 796777-001 (6) C13 & (2) C19, L6-20R (8) C13 & (1) C19 AF455A R/T 3KVA UPS, 2U, DTC, HV, INTL KIT 517701-001 SPS-UPS,R3KVA, DTC, 2U, INTL 881410-001+ Batt. 796777-001 (6) C13 & (2) C19 (8) C13 & (1) C19 The R/T3000 G5 UPS uses different internal batteries than the R/T3000. R/T3000 G5 battery: 796777-001 R/T3000 battery: 517703-001 The R/T3000 G5 Extended Runtime Module is different from the R/T3000. A customer's existing R/T3000 Extended Runtime Module (517702-001) will NOT function with the R/T3000 G5. The R/T3000 G5 requires a 796762-001 Extended Runtime Module. Runtime (under full load): R/T3000 runtime is 5 min R/T3000 G5 runtime of 3 mins Communication card: R/T3000 uses HP Management Card AF401A R/T3000 G5 uses a Q1C17A Software User Interface: R/T3000 uses HPPM (HP Power Management) R/T3000 G5 uses HPEPP (HPE Power Protector) Replacing the R/T3000 G2 with R/T3000 G5 models When the R/T3000 G2 UPS units are replaced with the R/T3000 G5 UPS, there are six differences between both UPS units: Front panel cosmetic differences. The R/T3000 G5 UPS is cosmetically different from the R/T3000 G2. See the illustrations below for reference only. R/T3000 G2 vs R/T3000 G5 Rear panel receptacles and cable differences. See the following illustrations for reference only. R/T3000 G2 vs R/T3000 G5 The R/T3000 G5 UPS has a different quantity of rear panel outlets. Refer to the Table below: R/T3000 G2 to R/T3000 G4 Compatibility Matrix R/T3000 G2 Option Kit R/T3000 G2 Option Kit Description R/T3000 G2 Spare Unit R/T3000 G2 Spare Unit Description Replacement Alternative R/T3000 G5 Unit Spare R/T3000 G2 Output Receptacles Alternative R/T3000 G5 Output Receptacles AF466A R/T 3KVA UPS, 2U, L530, LV, NA/JPN G2 KIT 638840-001 SPS-UPS, R3KVA, L5-30P, 2U, NA/JPN 881408-001+ Batt. 796777-001 (4) 5-20R & (1) L5-30R (6) 5-20R & (1) L5-30R AF467A R/T 3KVA UPS, 2U, L620, HV, NA/JPN G2 KIT 638841-001 SPS-UPS, R3KVA, L6-20P, 2U, NA/JPN 881409-001+ Batt. 796777-001 (6) C13, (2) C19, L6-20R (8) C13 & (1) C19 AF468A R/T 3KVA UPS, 2U, DTC, HV, INTL G2 KIT 638842-001 SPS-UPS,R3KVA, DTC, 2U, INTL 881410-001+ Batt. 796777-001 (6) C13 & (2) C19 (8) C13 & (1) C19 The R/T3000 G5 UPS uses different internal batteries as the R/T3000 G2. R/T3000 G5 battery: 796777-001 R/T3000 G2 battery: 517703-001 The R/T3000 G5 Extended Runtime Module is different from the R/T3000 G2. A customer's existing R/T3000 G2 Extended Runtime Module (517702-001) will NOT work with the R/T3000 G5. The R/T3000 G5 requires a 796762-001 Extended Runtime Module. Runtime (under full load): R/T3000 G2 runtime is 5 min R/T3000 G5 runtime of 3 mins Replacing the R/T3000 G4 with R/T3000 G5 models When the R/T3000 G4 UPS units are replaced with the R/T3000 G5 UPS, there are 2 differences between both UPS units: Front panel cosmetic differences. The G5 RT3000 UPS is exactly the same UPS as the G4 RT3000 UPS, except for the following changes: New front bezel with the HPE green rectangle logo element R/T3000 G4 vs R/T3000 G5 Communication cards: R/T3000 G4 uses the AF465A R/T3000 G5 uses the Q1C17A NOTE: Products sold prior to the November 1, 2015 separation of Hewlett-Packard Company into Hewlett Packard Enterprise Company and HP Inc. may have older product names and model numbers that differ from current models. RECEIVE PROACTIVE UPDATES : Receive support alerts (such as Customer Advisories), as well as updates on drivers, software, firmware, and customer replaceable components, proactively via e-mail through HPE Subscriber's Choice. Sign up for Subscriber's Choice at the following URL: Proactive Updates Subscription Form. NAVIGATION TIP : For hints on navigating HPE.com to locate the latest drivers, patches, and other support software downloads for ProLiant servers and Options, refer to the Navigation Tips document . SEARCH TIP : For hints on locating similar documents on HPE.com, refer to the Search Tips Document .